EtherNet/IP ​

About 21 min read

The EtherNet/IP protocol lets 2WinScada communicate with PLCs, drives, remote I/O and similar devices that use CIP (Common Industrial Protocol). 2WinScada supports two communication paths:

  • Explicit messaging: Reading and writing with a request/response model over TCP port 44818. Identity, parameter, diagnostics and tag access use this path.
  • Implicit / cyclic I/O: A separate I/O connection is opened with the device, and Input/Output Assembly data is transferred continuously over UDP port 2222 at a set period (RPI).

Main supported features:

  • Generic CIP: access to the CIP objects (class / instance / attribute) and Assembly data given in the manufacturer's documentation
  • Rockwell / Allen-Bradley Logix (ControlLogix, CompactLogix): symbolic tag read/write, array elements, atomic members inside UDTs
  • Omron NX/NJ: symbolic read/write of network variables published for external access
  • Discovering EtherNet/IP devices on the network and testing the connection
  • Browsing tags on Rockwell Logix controllers and bulk import
  • Reading and writing a single bit inside an integer as Bool
  • Pulse and Rising edge command behaviors for Bool tags

Safety

Before trying write operations on production equipment, verify the manufacturer's documentation, process safety, user permission and the operating state of the device. Even if 2WinScada makes access possible, not every CIP object or tag is writable. CIP Safety, CIP Motion and CIP Security are not supported; do not use EtherNet/IP communication in place of a safety function.

License ​

EtherNet/IP is available in the Standard and Professional license editions; it is not available in the Starter edition. If the license does not include EtherNet/IP, saved EtherNet/IP definitions are not deleted, but creating, updating and duplicating definitions, connection tests and runtime communication are blocked. For license details, see the License page.

Device profiles ​

The Device profile field in the device definition determines how addresses are interpreted and how data is encoded.

Device profileUseSupported address types
Generic CIPAny EtherNet/IP device whose CIP object map is given in the manufacturer's documentation (drive, remote I/O, valve terminal, robot controller, gateway, etc.)CIP Object, Assembly
Rockwell LogixControlLogix and CompactLogix (1769/5069) controllersSymbolic, CIP Object, Assembly
Omron NX/NJNX/NJ CPUs with network variables published for external access over EtherNet/IP in Sysmac StudioSymbolic, CIP Object, Assembly

TIP

The Rockwell Micro800, MicroLogix, SLC and PLC-5 families are not supported with the Rockwell Logix profile. For the Generic CIP profile, take the service, class, instance, attribute or Assembly information and the data types from the device manufacturer's documentation; there is no single universal Assembly number.

Channel Definition ​

A channel holds EtherNet/IP devices that share the same timeout and concurrency settings. On the General tab of the new channel window, enter the channel name and select EtherNetIp as the Connection Type. The default values are a safe starting point; change them after measuring the network delay on site.

Connection Parameters tab:

FieldDescriptionDefaultRange
Connect timeout (ms)Time to wait for the TCP connection and session registration5000100–120000
Read timeout (ms)Time to wait for a read response3000100–120000
Write timeout (ms)Time to wait for a write response3000100–120000
Default polling interval (ms)Default read interval for tags100050–3600000

Advanced Parameters tab:

FieldDescriptionDefaultRange
Reconnect delay (ms)Wait before the first reconnection attempt after the connection is lost1000100–300000
Retry countLimits how many steps the reconnection wait time can grow50–100
Maximum concurrent requestsNumber of requests the channel can send at the same time41–32

TIP

Retry count does not stop reconnection attempts; it only limits how much the wait time increases. The wait time grows up to at most 300 seconds, and attempts continue until the device connects.

Device Definition ​

A device record represents a physical or simulated EtherNet/IP endpoint. On the General tab, the device name and Active are set as for other protocols.

Parameters tab:

FieldDescriptionRule
Host / IP addressIPv4/IPv6 address or DNS name of the deviceRequired; at most 253 characters
PortEtherNet/IP TCP portDefault 44818; 1–65535
Device profileGeneric CIP, Rockwell Logix or Omron NX/NJRequired; determines the address and data encoding behavior
CIP route pathPort/link value pairs for routing through a chassis or bridgeOptional; see the description below

The CIP route path consists of comma-separated port/link value pairs. Values can be written in decimal (1,0) or in hexadecimal with a 0x prefix (0x01,0x00). The number of values must be even; at most 32 pairs can be entered. It is usually left empty when connecting directly to a CPU or to a Generic CIP device. In a ControlLogix chassis, 1,0, 1,1 and 1,2 are used for the CPU in slot 0, 1 and 2 through backplane port 1. Verify the actual path for the site topology against the manufacturer's documentation.

Settings tab:

  • Enable Implicit / Cyclic I/O: Opens the cyclic I/O connection. When selected, the cyclic I/O fields appear (see Implicit / cyclic I/O).
  • Use native Logix bit writes when supported: Appears only with the Rockwell Logix profile and is on by default. When writing to bits of Logix symbolic integers, it uses the atomic mask operation in the controller; unrelated bits are preserved on the controller side. If the controller reports that it does not support this service, 2WinScada reads the value again and switches to a sequential read-modify-write method. After a timeout or another error, the write is not repeated. To always use read-modify-write, clear the option; this method does not protect against other systems writing to the same value at the same time.

The Advanced Parameters tab contains the expected identity information for the Generic CIP profile. These fields are optional (0–65535):

  • Expected vendor ID
  • Expected device type
  • Expected product code

If cyclic I/O is enabled, the same tab also contains the advanced cyclic I/O settings.

Device discovery ​

The Discover devices button in the device window lists the EtherNet/IP devices on the network:

  1. Select an active IPv4 network interface of the 2WinScada server from the Network interface list.
  2. Set the listening time (250–10000 ms, default 2000 ms) and click Start discovery. 2WinScada broadcasts a single identity query to the subnet of the selected interface and lists the responses. You can stop the operation with Cancel discovery.
  3. The list shows Source IP address, Product, Vendor ID, Product code, Revision, Serial number and Suggested profile. Rockwell Logix is suggested for devices with vendor ID 1, Omron NX/NJ for vendor ID 47, and Generic CIP for the others.
  4. If needed, choose a different profile in the Device profile (manual override) field and click Use selected device.

The address and profile of the selected device are copied to the device form; the device is not written to the database until the form is saved. Invalid responses are ignored without hiding valid devices, and their number is reported.

Connection test ​

The Test connection button validates the entered settings, connects to the device, opens an EtherNet/IP session and reads the device's identity information. If cyclic I/O is enabled, it also opens the I/O connection and closes it immediately to validate the Assembly, RPI and port settings; this test sends no output data.

  1. Enter the channel and device settings.
  2. Click Test connection and wait for the result.
  3. Compare the returned identity information (product, vendor ID, product code, revision, serial number) with the device label or project.
  4. Only then enable the device and allow write operations.

When the test fails, only a general error message appears on the screen; the technical details are in the service log. A successful connection test does not validate the address or data type of every tag.

Implicit / cyclic I/O ​

In cyclic I/O, 2WinScada is the side that opens the connection (Originator), and the field device has the Adapter role. The Input Assembly is transferred from the device to 2WinScada (T→O), and the Output Assembly from 2WinScada to the device (O→T). The fields appear step by step: first select Enable Implicit / Cyclic I/O; the output fields appear only if Enable cyclic outputs (O→T) is also selected.

WARNING

Cyclic I/O can be used only when the CIP route path is empty, that is, when the adapter is directly reachable. Output Assembly data can directly control physical equipment. Before enabling cyclic outputs, verify the manufacturer's Assembly definition, the safe state (failsafe) behavior, the Run/Idle requirement and every mapped output bit.

Fields on the Settings tab:

FieldDefault / rangeDescription
Input Assembly instance (T→O)1–4294967295Assembly number of the input data produced by the device
Input Assembly size (bytes)1–32768Size of the application data only
Input RPI (ms)100; 10–60000Period at which the device sends input data
Input connection typePoint-to-pointPoint-to-point or Multicast
Enable cyclic outputs (O→T)OffSeparate safety switch for output traffic
Output Assembly instance (O→T)1–4294967295Assembly number of the output data consumed by the device
Output Assembly size (bytes)1–32768Size of the application data only
Output RPI (ms)100; 10–60000Period at which 2WinScada sends output data
Output connection typePoint-to-pointPoint-to-point or Multicast
Configuration Assembly instance (optional)EmptyConfiguration Assembly number expected by the device
Configuration data (hex, optional)Empty; at most 488 bytesTwo-digit hexadecimal values; e.g. 01 02 or 01-02

Fields on the Advanced Parameters tab:

FieldDefault / rangeDescription
Input uses Run/Idle headerOffWhether the input data is preceded by a 4-byte header
Output uses Run/Idle headerOffWhether a 4-byte Run/Idle header is added in front of the output data (visible only when cyclic outputs are enabled)
Local IPv4 interface (optional)Empty = automaticLocal IPv4 address used for UDP communication
Local UDP port (0 = automatic)0; 0–65535In a multicast scenario, must match the port the device expects
Adapter UDP port2222; 1–65535I/O port of the device
Connection timeout multiplier44, 8, 16, 32, 64, 128, 256 or 512; the connection timeout is calculated as RPI × multiplier
Large ForwardOpen modeAutoAuto, Standard ForwardOpen only or LargeForwardOpen required
Originator vendor ID0; 0–65535Entered if there is a registered originator identity
Originator serial number (0 = automatic)0Entered if there is a registered originator serial number

Match the Run/Idle options for input and output separately with the device's EDS file or manual; a wrong choice causes packet size validation to fail. When Large ForwardOpen mode is Auto and the connection size exceeds 511 bytes, the large connection request is used automatically; when Standard ForwardOpen only is selected, connection sizes greater than 511 bytes are not accepted.

Cyclic I/O behavior:

  • If input data stops, only the quality of tags mapped to the input Assembly becomes Bad and the connection is reopened. If explicit messaging is healthy, it keeps working.
  • Cyclic outputs start with output data filled with zeros; areas not mapped to a tag stay zero.
  • The quality of a command tag mapped only to the Output Assembly may stay uncertain (Uncertain) until separate feedback comes from the device. Writing to an output does not confirm that the device applied the command; for confirmation, use a separate feedback tag mapped to the Input Assembly.
  • RPI accuracy depends on the operating system and network conditions; no hard real-time control guarantee is given.

Tag Definition ​

Tags are defined in the device's tag table in the same way as for other protocols (see Tag Management). On EtherNet/IP devices, the Address cell opens an editor that shows the parts of the address as separate fields. The editor builds the address to be saved from these fields; in the table the address appears as single-line text starting with eip:v1; (e.g. eip:v1;mode=symbolic;address=MotorSpeed;count=1).

The Address mode list has these options depending on the device profile:

  • Symbolic: Access by tag/variable name on the Rockwell Logix and Omron NX/NJ profiles
  • CIP Object: Access by class / instance / attribute
  • Assembly: Access to a byte or bit range inside the Assembly data

The Symbolic address mode cannot be used with the Generic CIP profile.

Symbolic addresses ​

FieldDescription
Symbol / tag addressTag or variable name in the controller; at most 200 printable ASCII characters
Element countNumber of elements to read from an array; 1–4096
Bit index (optional)Rockwell Logix only: bit inside an integer tag
Source data typeType of the integer when a bit is selected: SINT, INT, DINT or LINT

Rockwell Logix examples:

AddressExample typeMeaning
MotorSpeedRealController-scoped tag
Temperatures[3]RealArray element
Program:MainProgram.Motor01.SpeedRealProgram-scoped tag / atomic member of a UDT
OperatorMessageStringStandard Logix STRING, at most 82 ASCII characters

For Rockwell Logix:

  • Controller tags, program tags in the form Program:<ProgramName>.<Tag>, array indexes with up to 3 dimensions (e.g. Matrix[1,2]) and atomic members inside UDTs are supported.
  • A whole UDT is not decoded automatically; address the atomic member.
  • Data types that can be used with symbolic addresses: Automatic, Bool, Sbyte, Int, DInt, Real, LInt and String.
  • In the controller project, verify that the External Access setting of the tag allows the operation.

For Omron NX/NJ:

  • In Sysmac Studio, verify that the variable is published over EtherNet/IP (Network Publish) and check its type.
  • The address is a single variable name; structure members are not decoded automatically. Atomic types and CIP STRING are supported.
  • Request and response sizes are limited to 492/496 bytes; large arrays are not transferred in fragments.

The Automatic data type can be used only with Rockwell Logix and Omron NX/NJ symbolic addresses, and the tag must be marked Read Only.

CIP object addresses ​

FieldDescription
Class (hex)CIP class number, e.g. 0x64
InstanceInstance number (1 or greater)
Attribute (optional)Attribute number (1 or greater)
Bit index (optional)Bit inside an integer attribute

When the Technical details check box in the address editor is selected, these fields also appear:

  • Service (hex): Default 0x0E (Get Attribute Single). On write, 0x0E is automatically changed to the 0x10 (Set Attribute Single) service. 0x01 (Get Attributes All) is read-only and takes no attribute number. Other services in the 0x01–0x7F range are validated and used unchanged; they require the manufacturer's service definition.
  • Source data type: Type of the integer when a bit index is entered (see Bit access).

Example: for a temperature value, Class (hex) 0x64, Instance 1, Attribute 1, Data Type Real. On ABB FENA adapters, drive parameters are read with class 0x90: Instance is the parameter group and Attribute is the parameter index (e.g. Instance 99, Attribute 1 for 99.01). This is explicit parameter access; it does not mean cyclic I/O.

Assembly addresses ​

FieldDescriptionRange
InstanceAssembly number1–4294967295
Byte offsetByte where the data starts0 or greater
Bit offset (optional)Bit inside the selected byte; Bool tags only0–7
Byte lengthByte range to read1–32768

When cyclic I/O is off, Assembly addresses are read with explicit messaging. When cyclic I/O is on:

  • Tags mapped to the Input Assembly instance number are updated from the incoming input data and must be Read Only.
  • Tags mapped to the Output Assembly instance number build the output data; they must be writable and their bit/byte ranges must not overlap.
  • Each tag must stay within the defined Assembly size. Other Assembly numbers can still be used for explicit access.

Example input mapping (8-byte Input Assembly):

PositionTagData TypeAccess
Byte offset 0, Bit offset 0RunningBoolRead Only
Byte offset 0, Bit offset 1FaultBoolRead Only
Byte offset 2, Byte length 2SpeedIntRead Only
Byte offset 4, Byte length 4CounterDIntRead Only

Bit access ​

A single bit of an integer value can be read and written as a Bool tag. When a bit is selected, the tag's Data Type is automatically set to Bool.

  • CIP Object: The service must be 0x0E. The Source data type can be SINT, USINT, INT, UINT, DINT, UDINT, LINT, ULINT or LWORD; the valid bit range is 0–7, 0–15, 0–31 or 0–63 depending on the source width. If no source type is selected, UINT (16 bits) is assumed.
  • Symbolic (Rockwell Logix only): The source can be SINT, INT, DINT or LINT; Element count must be 1.
  • Assembly: Bit offset is between 0 and 7.

When writing a bit, 2WinScada reads the current integer value from the device, changes only the target bit and writes the value back, preserving the other bits. On Rockwell Logix, if Use native Logix bit writes when supported is on, this is done atomically on the controller side. In other cases, the read-modify-write method does not fully protect against the PLC program or another system changing the same value at the same time.

CIP object bit tags that use the same integer source (the same address mode, service, class, instance, attribute and source type) are updated with a single read from the device. The shortest Update Interval determines how often the source is read; slower tags are updated when their own interval expires.

Tag fields ​

FieldEtherNet/IP rule
Data TypeMust match the actual CIP type on the device (see Data types)
LengthCharacter capacity for String tags (1–8192); number of array elements for other types (1–4096)
Update Interval[s]0.05–3600 seconds
Read OnlyIf selected, 2WinScada does not write to this tag
Command behaviorNormal write, Pulse (0 → 1 → 0) or Rising edge (0 → 1)
Pulse duration (ms)Only when Pulse is selected; 50–60000 ms, default 500 ms

The Read Only setting limits writing only on the 2WinScada side. A read-only attribute or tag on the device cannot be written even if it is left writable in 2WinScada. During initial commissioning, define tags as read-only and enable writing only after controlled verification.

Data types ​

CIP type2WinScada Data TypeSizeNote
BOOLBool1 byteAll profiles
SINTSbyte1 byteAll profiles
USINTByte1 byteOmron / Generic CIP; Byte and a length for byte arrays
INTInt2 bytesAll profiles
UINTWord2 bytesOmron / Generic CIP
DINTDInt4 bytesAll profiles
UDINTDWord4 bytesOmron / Generic CIP
LINTLInt8 bytesAll profiles
ULINTULInt / LWord8 bytesOmron / Generic CIP
REALReal4 bytesAll profiles
LREALLReal8 bytesOmron / Generic CIP
STRINGStringVariableRockwell standard STRING at most 82 ASCII characters; Omron CIP STRING
Type read from the deviceAutomatic—Rockwell / Omron symbolic read only

TIP

The configured type must match the actual data representation on the device. For Rockwell Logix symbolic addresses, the Byte, Word, DWord, ULInt, LWord and LReal types do not appear in the list.

Command behavior (Pulse / Rising edge) ​

The tag table of EtherNet/IP devices has Command behavior and Pulse duration (ms) columns. Command behavior can be used only on writable, single (non-array) Bool tags and with explicit messaging. Tags mapped to cyclic I/O Assemblies, advanced tags, arrays and CIP services other than 0x0E do not accept this behavior.

  • Pulse (0 → 1 → 0): A true request writes false and then true to the target; after waiting for the Pulse duration, it writes false. The duration is measured after the true write is confirmed. While a pulse is running, new true requests are ignored and the duration is not extended.
  • Rising edge (0 → 1): Writes false, then true, and leaves the target active. If you need an automatic reset, choose Pulse.
  • A false request cancels an active pulse or resets the target.

Only users who have the Operate or Editor role and see the tag within their process group scope can send Pulse and Rising edge commands (see Tag Write Scope).

WARNING

On stop, deactivation, license loss, reload and communication errors, 2WinScada tries to reset the target; however, a reset cannot be guaranteed when the connection is lost. Network delay can lengthen the pulse duration. This feature is not a safety function or a precisely timed PLC output; precise timing must be done in the PLC program.

Rockwell tag browsing ​

In the tag table of a saved Rockwell Logix device, the Browse tags button lists the tags in the controller and imports the selected ones in bulk:

  1. Click Browse tags. If needed, enter text in the Search address or data type field and choose All scopes, Controller or Program as the Scope; then click Browse.
  2. Review the Symbolic address, Data type, Dimensions, Structure / UDT, Importable and Availability note columns in the list. Structure/UDT roots and unknown types appear in the list but cannot be imported.
  3. Select the rows to import and choose the conflict policy: Cancel whole import on conflict, Skip conflicting tags or Rename name conflicts. Renaming only resolves name conflicts; an existing address is not added a second time.
  4. Click Import selected tags. The selected tags are validated and saved in one go; no log or alarm definition is created automatically.

The Omron NX/NJ and Generic CIP profiles have no automatic tag browsing; define the tags manually according to the manufacturer's documentation.

Read, write and connection behavior ​

  • Tag values are updated only when the value read changes.
  • On a timeout, when the device is offline or on a network outage, the quality of the affected tags becomes Bad; the last values are not deleted.
  • 2WinScada keeps trying to reconnect until the device connects; the wait time increases with each attempt and reaches at most 300 seconds.
  • An address or configuration error specific to a single tag does not interrupt a healthy device session.
  • When the same error repeats, the first error is written to the service log in detail; repeats are summarized every five minutes. If no new error appears in the log, it does not mean that the attempts have stopped.

Out of scope ​

  • Automatic tag browsing for Omron NX/NJ and Generic CIP
  • Automatic decoding of whole UDTs
  • Produced/Consumed tags
  • CIP Safety, CIP Motion and CIP Security
  • Cyclic I/O connections routed through a CIP route path
  • Automatic configuration of every EtherNet/IP device

Reusable tag templates for EtherNet/IP devices and creating profiles from EDS files are described on the Device Profiles page.

Troubleshooting ​

SymptomChecks
The connection cannot be establishedCheck the Host / IP address, TCP port 44818, VLAN/routing, the firewall, that EtherNet/IP is enabled on the device and the Connect timeout (ms) value.
A Generic CIP tag is not readCompare the service, class, instance, attribute and data type with the manufacturer's object manual; start with service 0x0E.
A Rockwell symbolic tag is not readCheck the spelling of the tag name, the controller/program scope, the External Access setting, the CIP route path value and the data type.
An Omron symbolic tag is not readCheck the variable's Network Publish setting, that the name is a single variable name, the supported atomic type and the message size.
Tag quality is BadLook for timeouts or network errors in the service log; allow time for reconnection.
Write failsCheck the Read Only setting, the user's permission, that the tag is writable on the device, the service/type match and the operating state of the device.
An array or string is truncated or rejectedCheck Element count, Length, the Rockwell 82-character limit and the Omron 492/496-byte limit.
Rockwell tag browsing stops or returns an errorCheck the device profile, the CIP route path value and access to the controller.
The cyclic I/O connection is rejectedCheck the input/output/configuration Assembly numbers, the byte sizes, the RPI range, the connection type and the device's concurrent connection limit.
Assembly size does not matchEnter the data size given by the manufacturer. In 2WinScada the size is the application data only; the Run/Idle header is selected separately.
No input data arrives, quality is BadCheck the firewall/VLAN path for UDP 2222, the Local IPv4 interface (optional) selection and the Adapter UDP port value.
Cyclic output does not workCheck the Enable cyclic outputs (O→T) setting, the output Assembly number and size, and that the output tags are writable and do not overlap.
Multicast does not workSelect the correct network interface; check IGMP and the switch settings. If needed, verify with Point-to-point first.
The RPI is not acceptedChoose a value in the 10–60000 ms range and within the limits the device supports.

2WinScada 2.10